JIS C3410 Collectively Screen LV Power and Lighting Cable

JIS C3410 Collectively Screen LV Power and Lighting Cable

 JISC 3410 LV Collective Screen Power Cable

JISC 3410 LV Collective Screen Power Cable

JISC 3410 LV Collective Screen Power Cable Application

This Cable can be applied in Marine&Offshore and various ships, ship repair and oil platforms and other offshore buildings control device and general electric lighting,machinery and equipment of factories and mines are also equally applicable.

JISC 3410 LV Collective Screen Power Cable Standards

JISC 3410-1999/2010
IEC 60332-1
IEC 60332-3 Cat.A(for FA-type)

JISC 3410 LV Collective Screen Power Cable Model

[FA-] SPYCS, SPYCBS, DPYCS, TPYCS, FPYCS
[FA-] SPYCYS, SPYCBYS, DPYCYS, TPYCYS, FPYCYS
0.6/1kV SPYCBS, FA- SPYCBS
0.6/1kV SPYCBYS, FA- SPYCBYS
0.6/1kV DPYS, TPYS, FA-DPYS, FA-TPYS
0.6/1kV DPYCS, TPYCS, FA-DPYCS, FA-TPYCS
0.6/1kV DPYCYS, TPYCYS, FA-DPYCYS, FA-TPYCYS

JISC 3410 LV Collective Screen Power Cable Structure

JIS C3410 Collectively Screen LV Power and Lighting Cable Diagram
JIS C3410 Collectively Screen LV Power and Lighting Cable Diagram

Conductor S(D,T) Tinned annealed stranded copper, class 2 according to IEC 60228
Conductor screen Semi-conducting compound
Insulation P 85°C EPR as per IEC 60092-351
Cabling Insulated conductors shall be cabled.
Flame retardant & non-hygroscopic fillers may be used
Overall shield S Tinned copper wire braid
Bedding Y PVC as per JIS C 3401
Armor C
(CB)
Galvanized steel wire braid(-C TYPE) or
copper alloy wire braid(-CB TYPE)
Sheath Y PVC as per JIS C 3401
Core identification 1C Black
2C Black, White
3C Black, White, Red
Outer sheath color Black

Installations recommendations

Minimum cable bending radius
The internal radius of cable bends which are not subjected to movements by expansion, is not to be less than :
6 times the external diameter of cable
Cable which are subjected to movements by expansion and the high voltage cable are to be bent to a form of at least 12 times cable diameter.
Installations temperature
Minimum recommended temperature of installations :
-10°C Ship wiring cable with PVC sheath
-20°C Elastomeric on/off shore cables
Installations pulling force
The cable pulling force can be estimated, as a maximum limit :5Kp per mm2 conductor area in the cable.Additional tension will be supplied from the braid and the insulation
and sheathing compound.